Pressure indicator PZ-200
- ●To make a purchase, contact Distributors, or use e-commerce below.
SALES CHANNEL ;Check our Distributors.- SALES CHANNELClick here to check our Distributors.
Pressure indicator PZ-200
- The compact design saves the space
- By VR, any pressure unit can be set to full scale
- With pressure switch function (4 points setting)
- Meets DIN sizes (72 × 72 mm)
- Input signal: 1~5 V or 4~20 mA
⦿ COMPATIBILITY WITH SENSORS
PZ-200 shall be used with Copal's pressure transducers with Amp. and other sensors whose output signals are DC1~5 V or 4~20 mA.
⦿Caution
Sensor that measures compound pressure can't be used with PZ-200. PZ-30 is suggested as alternative product.
STANDARD SPECIFICATIONS
- Unless otherwise specified, the specs are defined at an ambient temperature of 25 ± 5 °C and excitation voltage of 12 VDC.
General specifications | Operating temp. range | 0 ~ 50°C | |
---|---|---|---|
Compensated temp. range | 0 ~ 50°C | ||
Operating humidity | 35 ~ 85%RH (No condensation) | ||
Storage temp. | − 20 ~ 70°C(Atmospheric pressure, humidity 65 %RH maximum) | ||
Net weight | Approx. 150g | ||
Power | Power:12 ~ 24 V DC ± 10 % Consumption current: 80 mA maximum |
||
Imput | Input signal | 1 ~ 5 V/4 ~ 20 mA(Internal switch provided) | |
Input impedance | Approx. 120kΩ(1 ~ 5 V Input setting) | ||
Internal resistance | 51Ω(4 ~ 20 mA Input setting) | ||
Maximum input voltage | 30V | ||
Maximum input current | 70mA | ||
Display | No. of digits | 3 1/2 | |
Display element | LCD | ||
Rated display range | 0 ~ 1000 | ||
Display cycle | Approx. 4 times/s | ||
Display accuracy | ± 0.1 % Reading ± 2 counts(After calibration) | ||
Thermal error | Zero point indication | ± 3 counts/10 °C | |
Full scale indication | ± 3 counts/10 °C | ||
Resolution | 1 count | ||
Zero point variable range | ± 200 counts | ||
Full scale variable range | ± 200 ~ 1000 counts | ||
Decimal point location | 102、101、100(Selected by a panel switch) | ||
Polarity change | Negative “−” indication (actuated by panel switch) | ||
Over-range indication | “ 1*** ” when the numder exceeds ± 1999 ( * : OFF) | ||
Switch | Pressure setting range | 0 ~ 1000 | |
Number of setting points | 1(LL)、2(L)、3(H)、4(HH) 4-point output | ||
Switching capacity | 30 VDC、100 mA(NPN NPN open collector) | ||
Residual voltage | 1.2 VDC(at 100 mA of inflow currrent) | ||
Output status | 3 modes (Refer to pressure switch output function) | ||
Setting method | By setting VR | ||
Response | Approx. 100 ms | ||
Analog output | Current output:4 〜 20 mA, Accuracy:± 0.5 %F.S.(at 25 ± 5 °C)、 Load: 250 Ω maximum |
ENVIRONMENTAL CHARACTERISTICS
Test item | Test conditions | Permissible change |
---|---|---|
Vibration | Amplitude 1.5 mm P-P, 10 ~ 55 Hz, 3 directions for 2 hours each (packed) |
Pressure indication, switch setting and analog output variation: ± 1% F.S., maximum each. |
Shock | 98.1 m/s2 , 3 directions for 3 times each (packed) | |
Moisture resistance | 40 °C, 90 ~ 95 %RH, 240 hrs |
INSIDE OF A PANEL
OUTLINE DIMENSION
Unless otherwise specified, tolerance: ± 0.5 (Unit: mm)
※Please refer to the page of PG-200 series for panel cut dimension.
※All the “Common” connections are made inside.
CONNECTION OF PRESSURE SENSOR
※Shield should not be earthed when sensor is earthed.